Description
Characteristics
Technical Parameters
Characteristics

- Nozzle/baffle type resisting moisture, oil and dust.
- LCD display enables users to monitor the positioner status.
- PTM module and HART module is available.
- Various options for flow output setting: Linear, Quick Open, Equal Percentage and Users set (16 point).
- Easy for calibration and parameter setting.
Technical Parameters
| ITEM / MODEL | SWSP-25L | SWSP-25R | |
| Input Signal | 4 to 20mA | ||
| Supply Pressure | 0.14 to 0.7MPa | ||
| Stroke | 10 to 150mm;5 to130mm | 0°to 90 | |
| Impedance | Max.500Ω / 20mADC | ||
| Air Connection | PT(NPT)1/4 | ||
| Gauge Connection | PT(NPT)1/8 | ||
| Conduit | PF1/2 (G1/2) | ||
| Repeatability | ±0.5% F.S. | ||
| Ambient | Operating | -20 to 85℃ | |
| LCD Operating | -40 to 80℃ | ||
| Linearity | ±0.5% F.S. | ||
| Hysteresis | ±0.5% F.S. | ||
| Sensitivity | ±0.5% F.S. | ||
| Air Consumption | Below 2LPM (sup=0.14MPa) | ||
| Flow Capacity | 70LPM (SUP=0.14MPa) | ||
| Output Characteristics | Linear, Quick Open, EQ%, User Set(16 point) | ||
| Material | Aluminum Die-casting | ||
| Enclosure | IP66 | ||
| Explosion Proof | ExiambIICT6 | ||